Universal Quick Disconnect Couplings Supplier for Liquid Cooling

TICOOLFLOW supplies UQD manual and UQDB blind-mate quick disconnect couplings for rack manifolds, server cooling loops and modular liquid cooling assemblies. Compare series and specifications, then send your mating interface, operating conditions and quantity for project pricing. MQD / MQDB configurations are also available for review.

Manual & Blind-Mate SS304 / SS316L Options Water-Glycol Selection OEM Interface Review

Select by flow, pressure drop, mating interface, coolant and seal material. Confirm the exact interface specification and revision for your project; the UQD name alone does not establish cross-brand interchangeability or compliance.

UQD universal quick disconnect couplings for liquid cooling
UQD Series · Manual liquid cooling connections

Product Range

UQD, UQDB & NVQD Liquid Cooling Coupling Range

Quick disconnect configurations for rack cooling, blind-mate modules, cold plate loops, GPU cooling, and high-density server liquid cooling systems.

UQD series quick disconnect coupling

UQD Manual Quick Disconnect Couplings

Standard universal quick disconnect couplings for hose-to-rack, rack-to-manifold, and liquid cooling distribution applications.

  • Pressure: 6.9–20 bar by listed size
  • Size: 1/8" to 1/2"
  • Material: SS 316L / SS 304
  • Use: Manual quick connection
Download UQD Catalog →
UQDB blind mate quick disconnect coupling

UQDB Blind-Mate Quick Disconnect Couplings

Blind-mate floating quick disconnect couplings for behind-blade connections, hard-to-reach environments, and high-density server rack systems.

  • Pressure: Up to 20 bar depending on size
  • Misalignment: Radial compensation available
  • Material: SS 316L / SS 304
  • Use: Blind-mate connection
Download UQDB Catalog →
NVQD quick disconnect coupling for data center cooling

MQD / MQDB Series

Push-type fluid connectors for compact liquid cooling loops, single-hand operation, service connections, and compact cooling circuits.

  • Pressure: Up to 6.9 bar depending on configuration
  • Size: 1/8" to 1/2"
  • Material: SS 316L / SS 304
  • Use: Push-to-lock connection
Download MQD Catalog →
Selection Guide

UQD vs UQDB: Select a Connection for Your Cooling Assembly

Start with the connection method and available service access, then review hydraulic performance and the exact mating interface.

01 / Manual Connection

Review UQD where the coupling is accessible for connection and maintenance. Confirm release clearance, hose routing, retention and the required connection sequence.

02 / Blind-Mate Interface

Review UQDB for connections made as a module or tray is inserted. Confirm mounting arrangement, radial alignment, insertion force and engagement travel.

03 / Existing Interface

For NVQD / NVQDB or an existing supplier part, send the full part number and drawings. Size alone cannot establish mating compatibility or an approved replacement.

Include required flow, allowable pressure drop, connected and disconnected pressure, temperature, coolant formulation, seal material, end connection and quantity. Qualification should use the selected configuration’s current drawing and test requirements.

Product Videos

UQD / UQDB Quick Disconnect Demonstration Videos

Review the supplied connection and manufacturing demonstrations for data center liquid cooling components.

UQD Connection Demonstration

Demonstration of Universal Quick Disconnect connection behavior for liquid cooling applications.

Coupling Manufacturing Demonstration

Manufacturing footage supplied with the product reference; discuss your required blind-mate interface and alignment conditions.

Quick Coupling Manufacturing Process

Precision manufacturing process for stainless steel quick disconnect couplings.

UQD Technical Data

UQD Quick Disconnect Coupling Specifications

UQD reference data by nominal size
Size Body Size Nominal Flow Diameter Connected Pressure Rated Flow Cv Value Air Inclusion Max Fluid Loss Max
UQD021/83.16 mm20 bar / 290 psi2.1 lpm / 0.6 gpm0.330.004 cc0.007 cc
UQD041/46.3 mm16 bar / 232 psi6.4 lpm / 1.7 gpm1.370.024 cc0.01 cc
UQD063/87.9 mm6.9 bar / 100 psi11.4 lpm / 3.0 gpm2.370.027 cc0.022 cc
UQD081/210 mm6.9 bar / 100 psi17.8 lpm / 4.7 gpm5.320.029 cc0.03 cc
Data is provided for preliminary engineering reference. Confirm final performance by drawing, media, temperature, seal material, pressure, and test condition.

UQDB Technical Data

UQDB Blind-Mate Coupling Specifications

UQDB reference data by nominal size
Size Body Size Nominal Flow Diameter Connected Pressure Burst Pressure Rated Flow Cv Value Air Inclusion Max Fluid Loss Max Radial Misalignment
UQDB021/8"2.8 mm20 bar / 290 psi60 bar / 870 psi2.1 lpm / 0.55 gpm0.310.04 cc0.02 cc1 mm
UQDB041/4"5.5 mm16 bar / 232 psi48 bar / 696 psi6.4 lpm / 1.7 gpm1.220.04 cc0.025 cc1 mm
UQDB063/8"6.3 mm10 bar / 145 psi30 bar / 435 psi11.36 lpm / 3.0 gpm2.230.093 cc0.035 cc1 mm
UQDB081/2"7.9 mm10 bar / 145 psi30 bar / 435 psi17.8 lpm / 4.7 gpm3.760.096 cc0.044 cc1 mm

Values reproduced from the supplied product reference. Burst pressure is a test reference, not a permissible working pressure. Confirm size, alignment conditions, seals and current drawings before selection.

Applications

From Rack Manifold to Server Cooling Loop

Connection choices follow system layout, service access and coolant requirements.

AI & HPC Servers

Connections between rack distribution, flexible hoses and cold plate assemblies. Review flow demand and pressure drop for the complete supply and return circuit.

Rack Manifolds & Modules

Manual service connections or blind-mate module interfaces. Confirm mounting, alignment, engagement travel and maintenance clearance.

CDU & Hose Assemblies

Review coupling size and end connections with the cooling assembly drawing. Consider hose retention, routing and the permitted isolation procedure.

Water-glycol, dielectric and other engineered coolants require separate material and seal compatibility review. Low fluid-loss figures do not imply zero spillage, and service procedures must be confirmed for the system.

Engineering Review

Engineering Qualification for OEM & Project Procurement

Include the inspection scope and acceptance criteria in your inquiry.

Materials & Dimensions

Specify the body grade, seal compound, threads, mating dimensions and required material documentation.

Leak & Pressure Tests

Agree the test medium, pressure, temperature and acceptance limits for the selected assembly.

Flow & Service Cycles

Request available flow and pressure-drop data, connection force and cycle requirements for your project.

Product Questions

Universal Quick Disconnect FAQ

What is a Universal Quick Disconnect?

A UQD is a quick connection component used to connect and disconnect liquid cooling lines with controlled fluid loss and air inclusion. Select the exact mating configuration and operating limits for your system.

What is the difference between UQD and UQDB?

UQD refers here to manual connections. UQDB is a blind-mate series for module insertion and connections with limited direct access. Mounting and alignment requirements differ by configuration.

Does “universal” mean all brands are interchangeable?

No. Confirm the exact series, size, mating geometry, engagement method, materials, seals and qualification requirements before approving an alternative supplier’s part.

Which coolant and seal combinations can I request?

The supplied reference lists stainless steel body options and EPDM / FKM seals. Send the coolant formulation and concentration, temperature and pressure for compatibility review; a material name alone does not establish suitability.

How should I use the technical tables?

The tables reproduce the supplied UQD and UQDB reference data. Rated flow depends on test conditions, and burst pressure is not a working-pressure rating. Confirm the current datasheet for the exact configuration.

Can I request samples or a volume quotation for an OEM project?

Yes. Include the series, mating interface, evaluation quantity, estimated production demand and required delivery date in your inquiry. Sample availability, MOQ, documentation and lead time are confirmed for the selected configuration during quotation.

Does this page establish OCP compliance or approval?

No. If your project requires a particular OCP interface specification or other qualification, provide the document and revision. Request supporting documentation for the exact part; series names and reference performance tables do not establish compliance.

What should I include in an inquiry?

Send series, size, mating part number or drawing, coolant, operating pressure and temperature, flow and pressure-drop requirements, end connection, quantity and required inspection or qualification scope.

B2B Procurement

UQD / UQDB Supply for OEMs & System Integrators

Build your inquiry around the exact assembly and purchasing requirements. Sample availability, order quantity, delivery timing and documentation are confirmed during quotation.

Sample & Interface Evaluation

Send the mating part number, interface drawing and specification revision. Include sample quantity, test conditions and acceptance criteria for evaluation planning.

Project & Volume Quotation

Specify the required quantity, estimated project demand and target delivery schedule. Request confirmation of MOQ, availability and lead time for the selected configuration.

Assembly & Documentation Review

Provide hose or port connections, installation dimensions and required drawings, material documents and inspection records. Confirm the available scope with your quotation.

Get Started

Request UQD / UQDB Project Pricing

Send your series, size, mating part number or drawing, coolant, operating conditions and quantity. Include your sample qualification requirements and target delivery date so availability and project pricing can be confirmed.